| Cause | Inspection | Remedy |
|---|---|---|
| Defective Thermoswitch | The magnetic clutch switch turns off before the outlet air temperature is sufficiently low. | Replace the thermoswitch |
| Poor Expansion Valve temperature sensor contact |
The high and low pressure sides gauge pressures equalize when the magnetic clutch is turned off (within a short time duration) | Replace Compressor |
| Expansion Valve opens too far | Frost has adhered to the suction hose / pipe | Install the temperature sensor against the low pressure pipe and cover with insulating tape. |
| Clogged compressor suction filter | Compressor fitting is cool but the low pressure hose is not. | Remove and clean the filter. |
| Cause | Inspection | Remedy |
|---|---|---|
| Insufficient Refrigerant | There is little temperature difference between the low and high pressure sides. | Repair any leaks and recharge the refrigerant to the correct levels. |
| Clogged liquid tank (receiver dryer, accumulator) |
Considerable temperature difference between the inlet and outlet sides of the receiver dryer during operation. Also, tank may be frosted | Replace liquid tank (receiver dryer) |
| Clogged expansion valve | Expansion valve inlet side is frosted. Generally the low side pressure is near vacuum. | Replace expansion valve. |
| Expansion valve temperature sensor gas leak (damaged capillary tube, etc..) |
Expansion valve outlet side is chilled and low pressure side is LOW. | Clean or replace expansion valve. |
| Clogged or blocked piping | Low pressure readings decrease or a negative reading is shown. Indicates piping is clogged or blocked between the evaporator coil and the compressor. A frost spot may indicate the point of blockage. | Clean or replace piping. |
| Defective thermoswitch (cold control) |
Evaporator is frozen showing ice along the face of the coil, not just frost on the manifolds of the coil. | Adjust temperature sensing tube to a cooler part of the coil or replace the thermoswitch. |
| Cause | Inspection | Remedy |
|---|---|---|
| Poor Condenser cooling | Dirty or clogged condenser fins, Cooling fans do not operate correctly. | Clean and / or repair the condenser core / fans. |
| Excessive refrigerant | Verify by gauge reading | Utilize your refrigerant recovery equipment to capture excess refrigerant. Charge to the correct refrigerant levels. |
| Air in the system | Pressure is high on both high and low sides | Evacuate, vacuum and recharge with refrigerant. |
| Cause | Inspection | Remedy |
|---|---|---|
| Insufficient refrigerant | Little temperature difference between the low and high pressures. | Repair any leaks and recharge the refrigerant to the correct levels |
Request Information |
ISO 9001:2008 | News |
|---|---|---|
| Perrin Manufacturing is committed to providing you with superior products and services; we renew this pledge through continual improvement of our products and motivation of our staff. We faithfully comply with all of the requirements of our ISO 9001:2008 Quality Management System, the most current edition of the standard. Beyond that, our highly trained quality staff persistently search for new ways to improve the effectiveness of our system. |
|